b 1 of 1
. Scii^Job#: 203032204,
C z Name: TRC Environmental Coiporation
1
Phase CQntrastMi£rosconxlPCMlFibeiJR£ailts
35052-0000-00017; New York City Law Department; 100 Church Street, AMBIENT
Flow Air Fiber Fibers
SciLab Client Cone.
Rate Duration Filtered Fields Fibers Density TWA
Sample # Sample # / Location Collected (Hters/min.) (min.) (Fibers/cc)
(liters) (Fibers/inni )
01 GSO313O3ASBAIR2OO1 03/13/2003 6.3 420 2650.2 100 3 3.82 < 0.001
20lh Floor Northwest Area
02 GS031303ASBAIR2002 03/13/2003 6.3 420 2650.2 100 3 3.82 <0.001
20th Floor Northeast Area
03 GS031303ASBA1RPB01 03/13/2003 0 0 0 100 0.5 0.64
Field Blank Footnotes: /
Reporting Notes: /
(1) Fibers/cc cannot bfe with no air volume.
Analyzed by: Victor Slopac t/ Z'A_U<Z^^^^t<rXS^zed: 03/1V2003
Samples analyzed by NIOSH 7400(A) McihtKi, Issue #2, S/lsh^; Limit ol Detection- 5.5 fibers per 100 fields or 7 fibers/mnil; Blank analyses are reported -when available, however arc not used to adjust results of associated samples in this report. Titis
report rcliilcs ONLY to the sample analysis expressed as fibers/sq mm of filler area; ND=No fibers observed; NA= Not Analyzed; Walton-Beckett graticle field area = 0.00785 mini: TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr
period not sampled; Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to determine 95% certainty of compliance with the 0.01 fiber/cc standard; Estimated relative standard deviation: IntraJab Sr=0.405. biterlab
Sr=0.45, New York samples (NYSDOH ELAP Lab It 11480); National Institute of Standards and Technology Accreditation requirements mandate that tliis report must not be reproduced except in full without the approval of Ilie laboratory. A IHA # 102843.