Client Name: TRC Environmental Corporation
PhasejContrasLMicroscoBy(PCMlFiber.Re§uIt§
35052-0000-00007; New York Law Department; 100 Church Street/OSHA
Flow Air Fiber Fibers
SciLab Client Date Rate Duration Filtered Fields Fibers Density Cone. TWA
Sample # Sample # / Location Collected (liters/min.) (min.) (liters) (Fibers/mm'^ ) (Fibers/cc)
01 GS-3/16/02-OSHA-0207 3/16/02 2 390 780 100 12 15.29 0.008
Miguel Reynoso
02 GS-3/16/02-OSHA-0208 3/16/02 2 390 780 100 4 5.10 < 0.003
Wilfredo Ramirez
03 GS-3/16/02-OSHA-0209 3/16/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: 1
04 GS-3/16/02-OSHA-0210 3/16/02 0 0 0 100 0.5 0.64
Field Blank Footnotes; 7
Reporting Notes:
(1) Fibers/cc cannot be calculi for :s) with no air volume.
Analyzed by: Tatyana Grimchak Date Analyzed: 3/18/02
Samples analyzed by NIOSH 7400^ ^2, 8/15/94: Limit of Detections 5.5 fibers per 100 fields or 7 fibers/nim2: This report relates ONLY to the sample analysis expressed as fibers/sq mm of filter area: ND=No fibers observed: NA= Not
Analyzed; Walton-Beckett graticle field area - 00785 mm2: TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr period not sampled: Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to
determine 95% certainty of compliance with the OOl fiber/cc standard: Estimated relative standard deviation; Intralab Sr=0.405, Interlab Sr=0.45, New York samples (NYSDOH ELAP Lab # 11480): National Institute of Standards and Technology
Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. AIHA # 102843.
o
H
to
(—1
S
O
o
o
I
o
on
on
CO
NYC-WTC_000235323
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000235323Source: NYC Law Department, mirrored locally