01 GS7 1/28/02 5 360 1800 100 4 5.10 <0.001
6th Fl, Northeast Side Of Bldg
02 GS8 1/28/02 5 360 1800 100 16 20.38 0.004
6th Fl, Northwest Side Of Bldg
03 GS9 1/28/02 5 360 1800 100 8 10.19 0.002
3rd Fl, Northeast Side Of Bldg
04 GSIO 1/28/02 5 360 1800 100 12 15.29 0.003
3rd Fl, Northwest Side Of Bldg
05 GSll 1/28/02 5 300 1500 100 10 12.74 0.003
6th Fl, Northeast Side Of Bldg
06 GS12 1/28/02 5 300 1500 100 2 2.55 < 0.002
6th Fl, Northwest Side Of Bldg
07 GS13 1/28/02 5 300 1500 100 1 1.27 < 0.002
3rd Fl, Northeast Side Of Bldg
08 GSM 1/28/02 5 300 1500 NA
3rd Fl, Northwest Side Of Bldg Footnotes: 2
09 GS15 1/28/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: 1
10 GS16 1/28/02 0 0 0 100 0.5 0.64
Field Blank Footnotes: 1
Reporting Notes:
(1) Fibers/cc cannot be calculated for samples (or blanks) with no air volume.
(2) Analyst was unablgto quantify filler concentration because of overloading of particulate material on the filter.
Analyzed by: Devin Ahyee Date Analyzed: 1/29/02
Samples analyzed by NIOSH 7400(A) Method, Issue #2, 8/15/94; Limit of Detection= 5.5 fibers per 100 fields or 7 fibers/nini2: This report relates ONLY to the sample analysis expressed as fibers/sq nun of filter area: ND=No fibers observed: NA=Not
Analyzed; Walton-Beckett graticle field area = 0.00785 mm2: TWA = 8 Hr TWA calculation assumes zero exposure for remainder of 8 hr period not sampled: Upper 95% Confidence limit (Employers Compliance Test)- Calculated as a one sided UCL to
determine 95% certainty of compliance with the 0.01 fiber/cc standard: Estimated relative standard deviation: Intralab Sr=0.405, Interlab Sr=0.45, New York samples (NYSDOH ELAP Lab # 11480): National Institute of Standards and Technology
Accreditation requirements mandate tliat this report must not be reproduced except in full without the approval of the laboratory. AIHA # 102843.
NYC-WTC_000235481
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000235481Source: NYC Law Department, mirrored locally