of its past use in accordance with the Asbestos Hazard Emergency Response Act (AHERA), for
determining the effectiveness of asbestos abatement in schools. Modified-aggressive air sampling
w was also used because it is more representative of long-term trends of typical household activity
such as those expected within the study building.
While there is a greater potential for overloading under aggressive sampling conditions, this test is
representative of a worst case scenario. Modified-aggressive air sampling, however, has less of a
w potential for overloading and is typical of household activity patterns. (Difficulties associated
with sample overloading are discussed in detail in Section 3.8 below.)
Other post-cleanup sampling efforts were implemented to evaluate the efficiency of the cleaning
w
of the HVAC systems within the two commercial units included in the study (Chiropractor’s
Office, Mattress Store). Post-cleanup air samples were collected in close proximity to the HVAC
return ducts and analyzed for asbestos, MMVF, alpha-quartz and lead.
w
3.5 Sampling Supplies and Equipment
V
w Table 5.0 specifies the supplies and equipment required and utilized to collect samples, as
* described in the QAPP ' ’
Table 6.0 specifies the micro vacuum equipment and the National Air Duct Cleaners Association
(NADCA)-recommended method for sample collection that was used.
Table 7.0 specifies the air sampling equipment that was used.
«
<•
*
«•
” The QAPP is presented within Attachment G.