feet of floor. When directing the exhaust, caution shall be taken to minimize disturbance and potential damage
to furnishings and personal belongings.
Personal protective equipment including disposable clothing, gloves, and respirators shall be worn during
aggressive air sampling activities.
HVAC systems shall be shut down or isolated locally during aggressive air sampling.
Room and window air conditioners shall not be operated during aggressive air sampling.
Leaf blowers shall not be employed for modified aggressive air sampling.
All other procedures are identical for aggressive and modified aggressive air sampling, unless otherwise noted.
At least one 20-inch fan shall be placed in the center of each room sampled. One fan per 10,000 cubic feet of
room space shall be used. The fans shall be operated on slow speed and pointed toward the ceiling. The fans
shall run for at least 15 minutes prior to the start of sampling. The fans shall operate continuously throughout
sampling and shall not be turned off until sampling is completed.
Five samples will be collected per unit area. Sampling equipment shall be placed in living areas and away fi-om
obstructions. The sampling cassette must be placed on a tripod, not taped to existing surface and should be
directed downward at a 45 degree angle.
Common spaces will be sampled without the use of forced air devices (fans, leaf biowere etc). Five asbestos
samples will be collected in each apartment per floor. Sampling equipment shall be placed away from
obstructions. The sampling cassette must be placed on a tripod directed downward at a 45° angle and not taped
to existing surfaces.
Air samples will be collected in accordance with the procedures specified in NIOSH 7400 Method. The flow
rate for collection of air samples shall be at least 10 liters per minute and no more than 15 liters per minute. Air
sampling cassettes need to be monitored to ensure that the filters do not develop dark spots that would indicate
clogging. The minimum sampling volume required is 3600 liters. If clogging develops then the cassette must
be changed.
All clearance air samples and completed chain of custody forms must be submitted to the laboratory
immediately after sampling is completed.
A turn-around time of 24 hours is required for the analysis of asbestos post-clearance air samples.
Reporting ofLaboratory Sample Results
Asbestos Air Fiber Samples
All samples collected will be analyzed by the NIOSH 7400 Method, Counting rule “A.” The remaining portion
of the filter will be analyzed by AHERA Method which counts fibers >0.5 pm in length. The laboratory must
also record fibers >5u m in length to determine the PCMe value.
The PCMe Value is determined by counting all fibers >5pm with 3:1 aspect ratio by TEM.