NYC 9/11 Public Portal Document
OEM Swanke Hayden Connell Architects
7 World Trade Center
Project No.5576A Total RFI's Received 24
Revised 07/22/98 Total Responses Received 18
RFI LOG
RFI DATE SUBJECT/DIVISION/DWG NO. RESPONSE DATE # BUS DAYS Remarks
NO. REC'D RESP.
1 7/17/98 RETURN AIR DUCT ABOBE THE TYPE # 3 WALL BETWEEN FSK-1 WAS ISSUED ON 7/22/98 FOR PRICING OF OFFSET 7/22/98 4 FIELD CONDITION.
EOC AND CORR. INTERFERESC WITH FULL HT. (SLAB TO 3PLY WALL. AMBASSADOR TO PRICE MOVING AND/ OR
SLAB) PARTITION. PRVIDING NEW DUCT TO CLEAR WALL.
2 7/17/98 IN CORR. ADJACENT TO ROOM 23-43 THERE ARE (2) WET COLUMNS WILL BE FURRED OUT AS PER REVISED 7/22/98 2
COLUMNS WITH RISER PIPING ENCROCHING DRAWINGS, ISSUED FOR BULLETIN # 1 DATED 07/24/98 (
APPROXIMATELY 13" INTO CORR. VERBAL FIELD INSTRUCTIONS WHERE ISSUED 07/21/98)
3 7/17/98 IF R 7A IS TO BE BLAST PROOF. THE MANUFACTURER THE BgWiR IS HM, BUT THE SPECS CALL FOR LAMINATION 7/21/98 2
ADVICES THAT THEY CAN NOT PROVIDE WITH EMI OF VENEER THE SHIELDING COULD BE LAMINATED TO THE
SHIELDING. DOOR AND THEN COVERED WITH THE VENEER.
4 7/17/98 HURRICANE WALL CONTRACTOR WOULD LIKE SHCA TO SHCA WILL ACCEPT PANEL SYSTEM AS LONG AS 7/21/98 2 CANTOR HAS
CONSIDER ALT. PREFAB. PANEL SYSTEM. CONTRACTOR PROVIDES SHOP DRAWINGS AND ACCEPTED
STRUCTURAL CALCULATIONS THAT PROVE IS EQUAL TO DRETAILS FOR
DESIGN. STEEL PLATE
5 7/17/98 DOES CONC. CURB AT 7TH. FLOOR AND 23RD. FLOOR HAVE AS PER CONVERSATION WITH STRUCTURAL ENGINEER .11 7/20/98 3
TO BE CHOPPED INTO THE SLAB. CAN WE ACCOMPLISH THE IS NOT ACCEPTABLE TO SHOOT RODS OR ANCHORS TO
SAME THING BY DRIVING OR SHOOTING IN ANCHORS. SLAB.
6 7/31/98 DUCT INTEFERENCE WITH WALL BETWEEN CORRIDOR AND BUILD (2) LAYER WALL TO UNDERSIDE OF DUCT AND ADD 8/4/98 4
LIBRARY SOUND INSULATION ABOVE CEILING TILES A MINIMUM OF
2'-0" FROM WALL ON BOTH SIDES OF CORRIDOR.
7 7/31/98 DUCT INTEFERENCE WITH WALL BETWEEN CORRIDOR AND BUILD (2) LAYER WALL TO UNDERSIDE OF DUCT AND ADD 8/4/98 4
TRAINING ROOM. SOUND INSULATION ABOVE CEILING TILES A MINIMUM OF
2’-0’' FROM WALL ON BOTH SIDES OF CORRIDOR.
8 7/31/98 HEIGHT OF OUTLET SHOWN ON DWG. A-23-3 AND A-23-4 LOCATE OUTLETS AS PER DRAWING A-23-4 18" A.F.F. 8/4/98 4
DIFFER
9 7/31/98 OVERLY REQUESTED INFORMATION ON UL LABELS. ( DO NO THIS ARE NOT RATED DOORS. 8/4/98
LBR RS HAVE TO HAVE UL LAVELS.)
W.tOEMWocst RFI Logi xIs Printed S/10/98 3 12 PM Page 1
NYC-WTC_000173770
OCR can misread numbers and units. Confirm readings against the page image before using them.