JOB MEMORANDUM
TO: Mr. J. Majia SUBJECT; OEM
RFI N- 19,20 21 &22
EROM: Mt. V. Lemeshev
JOB NO: 1854
CC; Mr. Michael Maybapin
DATE; AufiustlO, 1998
The Following is rhe response to the above mentioned RFFs.
RFT 19
As it was conformed by Mr. M. Schneider of Ambassador Construction, this question is related
to the dampers installed at the protective wall and identified as “HD.”
Tliese dampers arc not purl of the .smoke control or smoke evacuation system etud does not
require status indication unless uiherwi.se requested by the user.
Please disregard re.spective section from onr response to RFI N“ 13.
RFl 20
As per the late.st request from The user, base price for the’TID” dampers shall be ba.sed on manual
damper.'; at the exterior protective wall and motorized dampers at the interior proieclive wall.
An add alternate will be based on all “JID" dampers to be electrically operated.
Dampers shall be controlled From the single switch.
Our drawing.s wilt be revised accordingly and reissued.
RFI N2 21
No. Proceed a.s per plans and specs.
RFT 22
To Follow.