balanced supply and demand, as defined for Light Hazard and Ordinary Hazard
areas in New York City Building Code Reference Standards RS 17-1 and RS 17-
2. Such drawings and calculations muyst be reviewed and approvaed by all
governing authorities. Fire Department, Owners Insurance Underwriters, Factory
Mutual and Industrial Risk Insureres before any work is c-omnienced at the
jobsite. ITie mains and risers supplying the fire department valves will remain as
sized on the drawings.
2. Subsection 2.4, Paragraph D
Revise to read as follows:
D. Provide stock of extra sprinkelr heads, sprinkler wrenches in accordance with
New Yoilc City Building Code Reference Standard RS 17-2,1989 Edition of
N.F.P.A. Pamphlet No. 13) Section 3-11.7. Cabinets shall be reliable or other
approved.
Section 15340
1. Subsection 1.4, Psiragraph A
Revise to read as follows:
A, Applicator; Company specializing in sprinkler installation with ten years
minimum experience.
1854.98\revpscc