5.6 Proposed Requirements for Fuel Oil Storage and Supply of
Emergency Power Systems
5.6.1 Fuel Oil Transfer Piping to Day Tanks
Requirement:
Fuel oil transfer piping to day tanks should be limited in diameter.
Commentary:
The size of fuel oil tanks ("day tanks") above the lowest level of a building is limited to a capacity
of 275 gallons. There have been reports of 12 inch diameter fuel oil piping installed to tanks on
upper floors in buildings. One foot of 12 inch diameter pipe has a volumetric capacity of about 5.8 ('
gallons. Thus, 47 feet of 12 inch pipe would equal 275 gallons. Obviously the use of a 12 inch
pipe is intended to provide reservoir capacity in excess of the 275 gallon limitation. Unfortunately,
the Building Code, as presently written, would not prohibit , the use of such oversized fuel oil
transfer piping.
5.6.2 Proposed Requirements on Fuel Oil Header Pipe Installations !
To be inserted into Article 17 27-829 (b) "exceptions."
Piping used for distribution of oil to fuel burning equipment.
Where piping is utilized for means of distributing fuel oil to equipment, without the use of a day.
tank, and where the piping is upsized to provide a storage capacity, the following requirements
shall apply.
1. All piping shall be suitably supported so as to not allow overstressing of piping and shall be
suitable isolated from rotating equipment.
2. All piping shall be schedule 40 steel.
3. Connections to main header (supply or return) shall be via the top of the pipe.
4. All fittings to header pipe and equipment shall be welded.
5. Fittings for immediate shut off valves to equipment shall be screwed or flanged.
6. Where air vents or vacuum breakers are required they shall be designed for the required use.
7. All air vents and vacuum breakers shall be hard piped to a local 55 gallon drum, with a leak
sensor alarm tied into a central alarm monitoring location. J
5.7 Proposed Revisions to Fire Protection and Egress Requirements
5.7.1 Exit Signs
Section 27-228.05 of article 26 of subchapter 1 administration and enforcement of chapter one of
title twenty-seven of the administrative code is identified as paragraph (a) and new paragraph (b) is added
as follows:
§[C26-125.1] 27-228.05 General Requirements.
(b) Owners of all existing buildings which are required to comply with paragraph fc) of section
. 27-383 (exit signagel shall File with the department a report prepared by a registered architect or
professional engineer certifying to the installation of the required exit signage no later than one year from
the effective date of this law.