Recommendation
6. Improve marking of the egress path, doors and stairs with photo-
luminescent materials and retrofit existing exit signs with either battery or
generator backup power
4.2.3 Planning and Training for Evacuation
The current NYC building and fire code requirements for occupancy group E, relative to
evacuations in the event of a fire, has consistently protected the safety of New Yorkers over the
decades. With regard to fire related emergencies, present evacuation requirements will remain
unchanged. However, the possibility of other unforeseen catastrophic events must be addressed
relative to evacuation.
i The Working Group discussed and determined there was a need for mandated, non-fire related
full evacuation plans. Currently partial evacuation plans and fire drills are required. This type of
planning and training will also help to confirm the use and availability existing egress paths such
as doors, stairs and roofs. Many building owners and managers have already begun full
evacuation planning and training. The Task Force recommends a requirement that all high rise
office buildings (occupancy group E) have full evacuation plans for non-fire related events.
Recommendation
7. Mandate a full building evacuation plan for non-fire related events.
4.2.4 Auxiliary Systems
Auxiliary egress systems and technologies that support and reinforce customary systems were
also discussed. Included in considerations were built systems such as fire towers and protected
vestibules at elevator lobbies along with new technologies such as so-called "Phase III" elevators.
The use of fire towers, an option in the current NYC Building Code, is in practice, discouraged
because the fire tower's floor area must be included as a part of the floor area ratio (FAR), a
calculation of a building's maximum floor area. A fire tower's area is counted as floor area, like
occupied space. To make the option of constructing fire towers more appealing, the Task Force
i recommends a FAR "subtraction" for fire towers. Buildings that include a fire tower should be
allowed to discount the floor area of the fire tower in the FAR permitted for development. This
recommendation would require a change in the Zoning Resolution and would have to be made in
conjunction with the Department of City Planning.
The mandating of protected vestibules at elevator lobbies was viewed favorably by the
Emergency Evacuation Working Group. Proposed legislation is included in the appendix.
Elevator evacuation is counter to the current standard restricting the use of elevators during an
emergency. Fire fighters and rescue personnel use elevators, during both fire and non-fire
emergencies. New technologies currently under development to build "Phase III" (waterproof and
smoke proof elevators suitable for use during emergencies) were discussed. Making
recommendations for the use of this nascent technology now, or in the near future, was seen as
premature by the Working Group. NIST will be studying this issue.