Seven World Trade Center o Outstanding Punch List Items

1. Tamper switches must be installed on the fire standpipe valves on the 44th floor and on the street level siamese connections.

2. The stair page system is not functioning properly. Every other. speaker in each stair riser is not audible. In Stair # 1 the speakers at the 37th and 41st floors are not functioning at all.

3. The following pertains to doors in stair # 2:

a. The door on the 45th floor must be realigned with the striker plate. b. The hardware on the 39th floor is loose and is scoring the door when it is operated. c. The door on the 38th floor does not close fully. d. The electronic striker on the 37th floor doesn't release upon emergency actuation.

4. The water level alarms for the 46th floor domestic water tanks have yet to be installed.

5. Elevator Banks C, D, and E must be tested for emergency recall on emergency power.

6. The emergency generators must be retested for a full load test for four hours. Apparently, the fuel is consumed by the generators at a faster rate than it is supplied. The generators ran for approximately two hours before running out of fuel.

7. Pressure differential/air velocity test on all duct smoke detectors in accordance with manufacturer's recommendations and the New York city Building Code.

8-. The window washing scaffold and rigging must be tested and inspected by New York State and the Port -Authority.

NYC-WTC 000166280

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000166280Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

FDNY CIDS form for 7 World Trade Center · Box FDNY

NYC-WTC_000169164

A Critical Information Dispatch System (CIDS) form from the Fire Department containing building data and contact information for 7 World Trade Center.

2 shared non-person entities · similarity 0.969

machine-extracted · confidence unavailable · Check page ↗

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000165980 · Box 7FDNY

Official violation order document issued by the FDNY Bureau of Fire Prevention directing correction of safety violations at a premises.

Similar indexed content

NYC-WTC_000166000 · Box 7FDNY

Official violation order document issued by the FDNY Bureau of Fire Prevention directing correction of safety violations at a premises.

Similar indexed content

NYC-WTC_000169205 · Box FDNY

Document summarizing fire service activities or inspections performed at the specified location.

Similar indexed content

Compare copies and versions →