← Document results/DEP Box 44/WORLD TRADE CENTER - RELOCATION OF RIVER WATER INTAKE LINES & PUMP STATION ELECT. POWER & COMM. LINES
Document / 132 pages

Foundation Specifications for WTC River Intake Relocation

Machine-extracted title · confidence 95%

Construction specifications document detailing foundation requirements for the World Trade Center river water intake system relocation project.

NYC-WTC_000165112–000165243

Folder label: “WORLD TRADE CENTER - RELOCATION OF RIVER WATER INTAKE LINES & PUMP STATION ELECT. POWER & COMM. LINES

Page image
Scanned page image, NYC-WTC_000165188
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Battex^l^ark City Commercial Center Bldg. ’B" WTC River Water Intake System Relocations

PART II - PRODUCTS A. NOT USED

PART III - EXECUTION A. Testing of 66^_ .0 Reinforced Concrete Pipe and 20”_ Prestressed Concrete Cylinder Pipe 1. After completion of installation of each new section of piping and before final connections are made, the lines shall be filled with water and hydrostatically tested for tightness. Each new section of piping shall be subjected to a test r-ressure of 125 Psig for a period of two (2) hours with no noticeable pressure drop. Back­ filling may be completed after hydrostatic test except where final connections are made to exist­ ing piping. 2. After final connections are completed, each new section of piping shall be subjected to a final hydrostatic test for tightness at the joints connecting to existing piping. A test pressure of 90 Psig shall be mfiintained for a sufficient period of time for the engineer to inspect each joint.. The Sub-contractor shall provide tempo­ rary pumping equipment to be located in the Port Authority Pump Station at the site for hydro­ static testing. 3. The Sub-contractor shall be responsible for the instai.lation and running of the pumping equipment and all temporary piping hook-ups. Each new section of piping shall require a separate tempo­ rary piping hook-up in the Pump Station and the point of connect.ion to existing piping shall be as directed by Port Authority. All work and operations performed by the Sub-contractor in the Pump Station shall be coordinated by the Port Authority and must have prior approval. The temporary pumping equipment- shall have aL water delivery rate of 500 gallons per minute at 90 Psig discharge pressure, and shall be <of the centrit/ugal typo, either engine or motor driven.

Pipe Testing, Examinations And Inspections 15040-3

NYC-WTC_000165188

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000165188Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000165064 · Box DEP Box 44

Request documentation regarding the relocation of river water intake lines and pump station utilities at the World Trade Center.

Filed in the same folder

Compare copies and versions →