Wipe Sampling Technicians Wipe sampling technicians must have 1 year experience in wipe sampling for a variety of contaminates. Employees shall have received state certified training in dust sampling. At a minimum at least 2 Wipe Sampling Technicians must be on staff.

Analytical Laboratory Environmental laboratory must be certified by the New York State Department of Health. Certification in each file following analytes must have been maintained for at least six consecutive proficient testing rounds: Asbestos Fibers in Air by PCM and TEM; Totals Metals including Mercury in Solid and Hazardous Waste and Dioxin in Solid and Hazardous Waste. Laboratory must possess a GC equipped with a capillary column and a high resolution mass spectrometer for analyzing Dioxin and an ICP for Total Metals. Analysis for Mercury must be done by cold vapor.

Proof of qualifications must be presented upon request by the DEP.

Specifications

This contract between DEP and the Monitoring Contractor shall be in force for 3 consecutive weeks from the commencement date. The monitoring contractor must be prepared to mobilize within 72 hours of the contract award. Cleaning activities shall be scheduled for residences per day. Air sampling shall be scheduled and completed within 24 hours of successful visual inspection by the Project Monitor.

Electricity needed to conduct air sample sampling must be provided by the owner or occupancy of the work area.

Sampling equipment must be in sufficient quantity to provide the amount and type of samples required for this project. At a minimum the following equipment are required: air-sampling pumps with maximum flow rate capacity of 15 liters per minute, tripods, rotometers, sample cassettes with mixed cellulose ester filters having pore size of O.Smicrons, disposable porous cellulosic towellette moistened with wetting agent and solvent-wetted sampling agent.

Laboratory must have all analytical instruments on site with sensitivities to the lowest level of detection as required by the analytical methods for each analyte.

All appropriate data, original field forms/data sheets, chain of custody forms and typed reports must be accurate and completed before submitted to DEP.

2 of 5

NYC-WTC_000163306

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000163306Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →