B. HVAC CLEANING SPECIFICATIONS:
1. The specifications state that the kitchen and bathroom exhaust systems are not included in this program. If not, under which program are they addressed?
2. The specifications allow the contractor to determine appropriate methods, tools and equipment required to do this project, rather than stipulating what needs to be done, how to do it, and what to use to get it done. This is, in a word, ludicrous.
3. The Inspector Qualification requirements, for the individual who will perform the HVAC cleanliness inspection (to determine if cleaning is even required), are incredibly vague. Also, are we to rely on just a visual inspection by this “qualified” person to determine if cleaning needs to be done or not? Why is there no provision for any sampling, as most of the contaminants that are present (i.e., asbestos fibers, dioxin, etc.) typically cannot be seen by the naked eye?
4. The NADCA standards that they continually refer to only apply to the general cleaning of HVAC systems and their related ducting, due to the typical build-up and deposition of normal dust that occurs over years and years of usage. This standard has absolutely no purpose being cited here since 1) the dust deposited within the various systems had nothing to do with their normal operation, and 2) the dust deposited is far from what would be considered normal. What we are dealing with in this situation is a dust that is, in general, far smaller in diameter than what we normally find in urban settings (therefore it was distributed throughout the area much more widely and efficiently) and contains numerous contaminants that would not normally be found in urban dust (including asbestos, RGBs, dioxins, etc., etc.).
5. Upon further examination, it appears that the HVAC cleaning specification that was “developed” is, in fact, a copy of the standard specifications that were developed by NADCA, with only minor revisions made to it. It is, in no way, site specific and fails to address the unique conditions that are present at 114 Liberty Street. For instance, the cleaning specification developed by the NYC DEP calls for all work to be done as an asbestos abatement project. The HVAC cleaning specifications, however, fail to even mention that asbestos is present. The HVAC cleaning specifications also fail to note that most, if not all, of the supply air ductwork is internally lined with fiberglass - an obviously porous material which cannot simply be decontaminated via HEPA vacuum techniques. Additionally, such a cleaning method for this type of material is not even allowed under the asbestos abatement regulations, and yet this specificatiorrlmplieslhat this would be acceptable. The specification also talks about cleaning return air ducts, even though there are none in any of the apartments.
NYC-WTC_000162615
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
Filed elsewhere
21 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000107585
Laboratory data table listing analytical results for various dioxin and dibenzofuran compounds with detection limits.
20 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000129376
Volume 1 of the final documentation report for the WTC unoccupied building monitoring program at 125 Cedar Street.
19 shared non-person entities · 1 shared topics · similarity 0.979
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000120991
Record documenting the transfer and custody of air samples from Building #100 at 345 South End Avenue collected on October 22, 2001.
9 shared non-person entities · 1 shared topics · similarity 0.969
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000120940
Document tracking environmental samples collected from Building #100 at 345 South End Avenue on October 22, 2001.
9 shared non-person entities · 1 shared topics · similarity 0.969
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000145027
Notice from NYC Law Department instructing staff to preserve World Trade Center documents for potential legal actions.
16 shared non-person entities · 1 shared topics · similarity 0.968
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000149432
DEP asbestos project notification form and inspection report dated December 12, 2002.
17 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000119908
Record documenting the transfer and custody of air samples from 365 South End Avenue collected on October 17, 2001.
8 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000125801
Cover sheet for a fax transmission from DEP regarding the 105 Duane Street site file.
12 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000117668
Chain of custody documentation for bulk sampling and air monitoring at 385 South End Avenue Building 500.
7 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000121462
Record documenting the transfer and custody of air samples from Building #500 at 385 South End Avenue collected on October 22, 2001.
9 shared non-person entities · 1 shared topics · similarity 0.965
machine-extracted · confidence unavailable · Check page ↗More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Buildings in this record
Machine-extracted building matches; verify each source. Buildings, never households.
- 114 Liberty Street · 3 pages · confidence 0.00 · verify page 3
- 125 Cedar Street · 7 pages · confidence 0.15 · verify page 11
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000162065
Notice instructing staff to preserve original World Trade Center documents as evidence for potential legal actions against the City.
Filed in the same folder
NYC-WTC_000162066
Daily summary of calls received by the WTC hotline on May 1, 2002, categorized by topic.
Filed in the same folder
NYC-WTC_000162067
Daily summary of calls received by WTC hotline operators on May 1, 2002, categorized by topic.
Filed in the same folder
Filed in the same folder
NYC-WTC_000162073
Daily summary of calls received by the WTC hotline on May 2, 2002, including requests for indoor air testing.
Filed in the same folder