B. HVAC CLEANING SPECIFICATIONS:
1. The specifications state that the kitchen and bathroom exhaust systems
are not included in this program. If not, under which program are they
addressed?
2. The specifications allow the contractor to determine appropriate methods,
tools and equipment required to do this project, rather than stipulating
what needs to be done, how to do it, and what to use to get it done. This
is, in a word, ludicrous.
3. The Inspector Qualification requirements, for the individual who will
perform the HVAC cleanliness inspection (to determine if cleaning is even
required), are incredibly vague. Also, are we to rely on just a visual
inspection by this “qualified” person to determine if cleaning needs to be
done or not? Why is there no provision for any sampling, as most of the
contaminants that are present (i.e., asbestos fibers, dioxin, etc.) typically
cannot be seen by the naked eye?
4. The NADCA standards that they continually refer to only apply to the
general cleaning of HVAC systems and their related ducting, due to the
typical build-up and deposition of normal dust that occurs over years and
years of usage. This standard has absolutely no purpose being cited
here since 1) the dust deposited within the various systems had nothing
to do with their normal operation, and 2) the dust deposited is far from
what would be considered normal. What we are dealing with in this
situation is a dust that is, in general, far smaller in diameter than what we
normally find in urban settings (therefore it was distributed throughout the
area much more widely and efficiently) and contains numerous
contaminants that would not normally be found in urban dust (including
asbestos, RGBs, dioxins, etc., etc.).
5. Upon further examination, it appears that the HVAC cleaning specification
that was “developed” is, in fact, a copy of the standard specifications that
were developed by NADCA, with only minor revisions made to it. It is, in
no way, site specific and fails to address the unique conditions that are
present at 114 Liberty Street. For instance, the cleaning specification
developed by the NYC DEP calls for all work to be done as an asbestos
abatement project. The HVAC cleaning specifications, however, fail to
even mention that asbestos is present. The HVAC cleaning
specifications also fail to note that most, if not all, of the supply air
ductwork is internally lined with fiberglass - an obviously porous material
which cannot simply be decontaminated via HEPA vacuum techniques.
Additionally, such a cleaning method for this type of material is not even
allowed under the asbestos abatement regulations, and yet this
specification implies that this would be acceptable. The specification also
talks about cleaning return air ducts, even though there are none in any of
the apartments.