WTC Daily Safety Report z
o 'Liberty
Mutual. o
i
i^ Report Period: 24 hours beginning 7:30 AM on >1.
co
o ■Q
o December 20th, 2001 c
o CT
o'
CD Obeervation/Hazard Location Corrective Action Required CM Person CM Response "D
o
O> Contacted
Drillers working on NW slurry wall In pit without respiratory protection AMEC Require respiratory protection In pit. Paul Difrenna Open. Issue was mentioned to workers In area
as well as Paul Difrenna. He stated that he will o
address the matter. o
o
AMEX building on 4th floor. Temporary lighting Is spliced with plug AMEC Temporary lighting should be improved and wired Paul Difrenna Open. Will look Into improvement. c
outlets. separately from temporary power. 3
o
Fall potential at hole east of WTC 6 location. Leading edge of recently AMEC Limit personneil access. Arsa needs to be protected until Ray Master Pending. Will limit access until the remainder of 3
collapsed bulldino subseouent demolltlen Is aeeomoliahed. WTC 6 fills the hole.
Cleveland tlebaok workers on wearlno respirators. Have workers wear respirators. JeffMelofchIck Closed
Falls horn elevation- laborer at 2nd level of AMEX building AMEC When working at elevations of 6' or more and outside of Duane Matters Closed- laborer tied off to retractible lifeline
ouardraH must haw PFA orevidsd.
Two ODC engineers In chiller area lacking Eye Protection. AMEC area near Use proper PPE. Names not given. Refused. Open. Refused to comply. Stated they wouldn't
chiller field Hard hat was marked Topo* leave the site to retreve glasses. Stated they
would wear them tn the future.
Iron worker not wearlno respirator. LLl.l I lit—KElye Worker? wee.r.rpgplrem. JeffMelofchIck Closed
Jersey barriers are not completely around opening and three wore not on Amec by WTC 8 and Place jersey barriers around opening and on solid JeffMelofchIck Open - Spoke to Jon who placed saw horses
solid ground. Vessey surface. and tape around the open until morning at which
time he indicated the barriers would be moved.
Hydro barriers rolled over and not protecting opening. Amec by WTC 8 and Upright barriers and replace caution tape. JeffMelofchIck Closed - Barriers where uprighted and caution
Vessey tape placed around Stem.
Mazzocchl Qrappler operator was not using his respirator. Amec In the pit arsa Orappler operators need to wear PPE. JeffMelofehiok Closed - Corrected on the spot
Truck Driver for Grace not wearing hard hat outside of vehicle. Amec on Vessey Operators outside of vehicles In the construction zone JeffMelofchIck Closed * Operator put PPE on his head.
should wear PPE._________________________
Seven workers In the AMEC area where not wearing PPE. AMEC Winter Garden Have workers utlilize respiratory protection. Paul Difrenna Open. Concrete chippers (Mazzocchl Laborers)
working without respirators. Spoke to crew,
foreman was not present Spoke to Paul
Difrenna. He stated that he will address the
niAffAr
Cleveland Dilling crew In pK not wearing PPE (respirators and safety AMEC/Cleveland Everyone.lnside slury wall Is required to wear respirators Duane Matters Open. Spoke with John, Cleveland foreman.
glasses) and safety glasses Said he would have his crew wear this.
Checked an hour later and half toe crew was stilt
wHhmit PPE
Mazzocchl operators refuse to wear respirators (# A26, At 1, A21, A27) AMEC/Mazzocchl Orappler operators need to wear PPE. Duane Matters Open, spoke with Chris at DDC and he spoke
with John. Mazzocchl Supt.
Fall hazard for surveyors at S.West comer of slurry wall Bovis Create safe work platform with handrails for surveyors Ray Master Open. R. Master stated he Is considering a work
platform with limited access with handrails
Hot work on one of the main chiller tank on 12/18. Potential acid gas povis York agreed (12/18) to submit a written procedure for Brian Peters and Ray Master Open. Plan being developed. Hot work permit
exposure from residual Freon-22. tank removal discussing toe recommended means and will be issued for other torch work in chiller area.
methods. DDC, LM and BOVIS will review and establish Tanks ars not to be out with torchs.
AftffAH nlflh fnr wAricAr DfAfAAttAn
Jersey barriers of West slurry wall (southern side) lacking walk path for Bovis Increase distance between slurry wall and Jersey barrier. Bill Ryan Open. Actual movement of barriers Is
top access. Creating difficult walk/work area Some barriers are lacking horizontal life lines. scheduled by Tully. Tully waiting fCr generators
(Q be moved.
Liberty Mutual Loss Prevention submitted 12/21/2001