NYC Law Department release
Independent mirror · updated as the City releases more · v1.2.6
← Document results/DEP Box 05/SCOPES OF WORK IN DOOR AIR & CLEANING
Document / 1 page

HVAC Scope of Work Addendum #2, WTC Dust, 2002

Machine-extracted title · confidence 100%

Addendum defining inspection scope for HVAC components at World Trade Center sites to assess dust accumulation.

NYC-WTC_000140298

Folder label: “SCOPES OF WORK IN DOOR AIR & CLEANING

Page image
Scanned page image, NYC-WTC_000140298
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ADDENDUM #2 World Trade Center Dust Cleaning Program Monitoring Contract Scope of Work

Determine the components that are accessible. At minimum, representative surfaces of the following system components should be inspected:

- air intake (outdoor or return) - air intake dampers - return air grilles - return air p lenum — horizontal surfaces - impingement points (e.g. turning vanes, elbows, transitions) - filter racks and filter media - blower - thermal coils - interior surfaces of the supply air ducts - horizontal surfaces - impingement points (e.g. turning vanes, elbows, transitions) - volume dampers - terminal boxes - supply diffusers

Note that depending on the size and complexity of the HVAC system, access may require the use of ladders, lifts or scaffolds using appropriate methods of fall protection.

6.5.1.2 Methods of Access

The following list summarizes methods of accessing HVAC system components for inspection;

- through existing service openings (i.e., access doors and panels) - by disassembly of housing - by installation of service openings (may range from 1” diameter holes to access doors)

The HVAC/Electrical Professional shall assess the accessibility of each HVAC system component to be inspected. If an HVAC system component is not accessible, the Environmental Professional shall be consulted to determine whether installation of a service opening will likely disturb asbestos-containing materials. After such consultation, if approved by the Environmental Professional, the HVAC/Electrical Professional shall install service openings as needed to inspect the HVAC components listed in 6.5.1.1.

NOTE: Disassembly of housing and installation of service openings may only be performed by the HVAC/Electrical Professional and replacement plates, panels or access doors shall be installed in accordance with NFPA, NADCA and SMACNA standards and NYC building codes.

NYC-WTC_000140298

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000140298Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000140281 · Box DEP Box 05

Draft contract scope defining regulations and procedures for asbestos cleanup and air sampling assistance programs in Lower Manhattan.

Filed in the same folder

Compare copies and versions →