Draft 2 Comments by Covino Environmental Associates. Inc. January 5.2003

may be used only if the system is sufficiently isolated and vacuum collection equipment is used to maintain a duct velocity of approximately 3'SBS feet per minute).

Use isolation/zone pillows as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone and to prevent cross-contamination of cleaned sections by work in sections not vet cleaned.

After cleaning, reinstall the bathroom or kitchen exhaust grille and cover again with polyethylene sheeting secured with painter’s tape to help maintain negative pressure within the exhaust ventilation system before moving on to the next grille. HEPA vacuum interior surfaces of the containment prior to dismantling or moving to another location. Place all waste in a 6 mil polyethylene bag for disposal.

40;Reinstall exhaust grills and-install one layer of 6 mil poly-ever grills-and seeure in place with painters tape.

11.Clean the main riser from the roof-or top most floor of the cleaning zone, using -a combination of techniques including whips, brushes, and compressed air.

12.Reinstall the mushroom once the riser-or top zone is cleaned. I □.Remove the poly barriers, covering-the exhaust grills, while the riser is-still imder negative pressure so that any loose dust or debris will be sucked down to the capture systesfc

14. Disengage the local capture system and relocate to another section of the riser or to another riser.

15. All work will be accomplished by a DEP certified Asbestos Handlers.

16. All work will be supervised by a DEP certified Asbestos Handler Supervisor.

17. Workers will utilize ^^face APR’s. eve protection and full body coveralls during the cleaning process.

18. Ensure that the occupant space is free of any debris associated with the duct cleaning process. Use HEPA vacuums and/or wet wiping to clean the space, as needed. Place waste and debris into double 6 mil polyethylene bags for removal as asbestos-containing waste.

NYC-WTC_000140026

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000140026Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →