Asbestos Abatement Technical Specifications For 130 Cedar Street, New York, NY and HEPA vacuuming with a funnel attachment. These procedures shall be limited to a maximum of one-foot wide strip spanning the length of the partition.

5.3 The Contractor shall clean all floors and dispose of any dislodged ACM in accordance with applicable regulatory requirements. Appropriate respiratory and protective equipment shall be worn during this operation.

6.0 HVAC Ductwork

This section refers to any uninsulated ductwork that passes through a containment area.

6.1 Any ductwork attached directly to the ceiling duct shall be positioned in such a way as to facilitate removal of the ACM above the duct. If this ductwork is removed It may either be:

a. Completely sealed with (2) layers of 6-mil fire retardant polyethylene, properly labeled and disposed of as contaminated.

b. Completely decontaminated inside and out, encapsulated, and disposed of as normal waste.

• 7.0 Light Fixtures

7.1 All light fixtures within the work area must be considered contaminated and treated as follows:

a. Lower light fixtures after isolation and critical barriers are in place.

b. HEPA vacuum and brush off gross contamination within the work area.

c. Wet wipe each fixture completely as it is taken out through the bag wash/wipe area. Each fixture must be thoroughly inspected for visible asbestos before being transferred to the clean area.

d. At the discretion of the Owner(s) either dispose of as waste or store all fixtures until work is complete.

e. When the area has been deemed clean, a qualified electrician may. reinstall the light fixtures.

7.2 If agreed upon by the Owner(s), used light fixtures will be double wrapped In 6-mil labeled and disposed of as contaminated waste.

7.3 If agreed upon by the owners and the Contractor, the light fixtures may • remain in place. If so the Contractor must abide by the following procedures.

a. Electrical power to the fixtures must be shut down and locked out.

Prepared by JLC Environmental Consultants, Inc. Project No. 04-3271 Page 41

NYC-WTC 000125619

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000125619Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000127738 · Box DEP Box 52

Health and safety plan for Phase I deconstruction at 133-135 Greenwich Street and 21-23 Thames Street dated June 8, 2005.

Cited alongside this record in an Ask answer

Compare copies and versions →