December 30, 2001
Mr. Nikes Miller
Dormitory Authority State of New York
One Penn Plaza, 52' Floor
Now "Fork, NY 10119
Subject; nvir onmental Testing (December 15 & 17, 2001)
Borough of Mxnhatta n Commmnity Cole
199 Chambers Street, New York, NY
PSI Project Number: 622-1A139
Dear Mr. Miller.
At the request of the Dormitory Authority State of New York, Professional Service Industries, Inc.
(PSI) has been directed to perform periodic environmental testing at the subject facility. The first
round of testing waft performed on September 28 and September 29, 2001. Results of all air and
surface testing for asbestos, lead, silica and dust at the time were below the established regulatory or
guideline levels for the selected analyte.
Due to accessibility Issues PSI has been unable to return to the facility for subsequent testing until
December 15 and December 17, 2001. Frequent periodic testing will Ire performed on the site until
further notice. PSI is working with BMCC facilities personnel to ensure full access to the site.
Monitoring performed on 12/15 and 12/17 includes testing for airborne asbestos, airborne silica,
respirable dust, selected airborne metals and Total Volatile Organic Compounds (VOCs),
preliminary testing results follow.
Mo oringAsbestos in Air
PSI collected 8 representative air samples from the Trailcra at the West Side Highway location. In
addition, 1 sample was collected from within the Gymnasium (north building) and 1 sample from
within Theater i (south building), as these areas were subject to use by emergencyhcscue workers.
Samples were collected and analyzed by Transmission Electron Microscopy in accordance with EPA
40 CFR Part 763 Final Rule (AHERA). AIdERA regulations establish the post abatement air
clearance criteria for asbestos abatement projects performed within schools (Grades K-12), The
AHERA post asbestos abatement clearance criteria is defined as an airborne asbestos fiber
concentration less than 70 structures par millimeter squared (<70 s/mm2). The samples collected are
not Intended to be post *abatement clearance samples, and the results have been compared to the
established AHERA criteria for the purposes of rcfereucing an established regulatory limit.
Laboratory analysis found no asbestos fibers present in any of the samples collected. Refer to Table
I for analytical results.