December 22, 2001
Mr. Edward Sullivan
Director of Operations
B.M.C.C.
199 Chambers Street
New York, New York 10007-1097
Re: Direct-Reading Measurements for fine dust particles
Dear Mr. Sullivan,
Tiffany-Bader Environmental, Inc. (TBE) performed direct-reading testing on December
19, 2001, for fine dust particles (2.5 m in diameter) in the portable classrooms, to
assess the performance of the portable HEPA filtered air cleaners. The sampling was
performed by Howard Bader, P.E., of TBE. At the time of sampling, the portable HEPA
filtered air cleaners had been installed in all the portable classrooms
Several buildings at and adjacent to the World Trade Center Complex in lower
Manhattan were destroyed or severely damaged on or around September 11, 2001. A
waste transfer operation is located directly across the street (West Street) from the
school building. It is suspected that debris from the initial building damage and waste
transfer operation is potentially contaminating areas in lower Manhattan with fine dust
particles. Past sampling by TBE had determined that the particulate levels in the
portable classrooms that did not have the portable HEPA filtered air cleaners were
higher than those that had the HEPA units. TBE's scope of work was to evaluate the
particulate levels in the portable classrooms now that the HEPA units were installed in
each classroom.
Fine Dust Particles Testing
TBE took realtime particle (aerosol) measurements in g/m3 at 2.5 m diameters
(PM2.5), using a TSI Model 8520 Dust Trak Aerosol Monitor. The Dust Trak is a laser
photometer, which uses light scattering technology to determine mass concentration.
The instrument has a sample flowrate of 1.7 Umin.
Based on the U.S. EPA's Air Quality Index, the level of concern for the general
population from exposure to fine dust particles at PM2.5 is 65 rg/m3 averaged over a 24