American Stock Exchange, 28 September 2001

86 Trinih Place Lead in Air Results Location Air Volume Liters Results µghn3 Post 2 Sec A Main Trading 1,200 < 5.0 Floor Post 8 Sec G Main Trading 1,200 < 5.0 Floor 15'' floor north side 1,200 397 12"' floor central 1,200 445 10"` floor central 1,200 < 5.0 7°' floor central 1,200 < 5.0 Harry's Trading floor 1,200 < 5.0

22 Thames Street Lead in Air Results Location Air Volume Liters Results ,ecglm3 Red room post 21 MFS 1,200 < 5,0 l0"' floor north side 2,450 <5.0 9°' floor central 1,580 9.0 7°' floor central 2,020 11.0

Except for the 15°' floor and the 12' floor these values are all less than the OSHA lead PEL of50 4g/m'. Before and during the time of air sampling the fire escape doors to these floors were left open all day and all night to cool the floor. It is believed that the lead its these samples blew in through the open fire escape doors and deposited on the filter media of the samples. We believe that the lead levels in these spaces were temporary and that they settled to the floor. The 1S" floor and 120f floor were re- sampled on September 29s', 2001, to more fully characterize the lead in air values.

The respirable dust (breathable) in air samples were collected from areas considered representative of the building. R.espirable dust samples were collected to show particle dust mass and the distribution of particle size. Only one sample was collected from each area to speed up th e building screening process. The respirable dust in air results are presented i:7 the tables below.

86 Trinity Place Resvirable Dust in Air Results Location Air Volume Results 1-5m 6-10/4m >10;.sm Liters Post 2 Sec C Main Trading 600 <5.0 `1% <0% <0% Floor

Page3of 9

NYC-WTC 000105114

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000105114Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →