e. For floor covering two layers of polyethylene sheeting shall be used. The first layer of floor sheeting shall extend up the wall at least 12 inches. The second layer shall be extended up walls at least 24 inches. Sheeting shall be located at the joints between walls and floors.
f. Wall sheeting shall consist of one layer of polyethylene sheeting. It shall be installed to minimize joints and shall overlap floor sheeting by at least 18 inches. No seams shall be located at the corners. Wall coverings shall be taped first to the upper most edge of the wall and shall hang straight down;
g. When a strippable coating is used in place of polyethylene sheeting, it must be manufactured for the specific application required for walls, floors, or windows:
When dry, the strippable coating must have a class A rating as a building material, and must meet the following requirements when tested in accordance with ASTM-E-84: flame spread no greater than 20, fuel contributed 0, and smoke developed no more than 110.
The strippable coating shall be applied uniformly in such a manner as to achieve a minimum uniform final thickness of six mil for each layer required pursuant to this subchapter.
Manufacturer's specifications shall be followed for the method of application and for the protection of the applicators and building occupants.
Use of the product shall be authorized in advance by the asbestos safety control monitor firm. The materials shall be delivered to the project site in unopened, factory-labeled containers.
h. As all existing ventilating systems in work area are to be sealed throughout the removal operation, an alternative system shall be utilized. Install approved HEPA equipped air filtration units with filters in place. HEPA equipped air filtration units shall be of sufficient number ran capacity to ensure that total air volume is exchanged at least once every 15 minutes and an acceptable pressure differential is established and maintained. These units shall be rated by the manufacturer as to their actual working air capacity and field tested pursuant to manufacturer's specifications.
Sequence of asbestos removal activities shall be as follows:
The asbestos-containing material shall be sprayed with water containing an additive to enhance penetration (amended water) or removal encapsulant. All wetting agents shall be tested on a small area before use to ensure effectiveness. A fine low-pressure spray of this solution shall be applied to prevent fiber disturbance preceding removal. The removal encapsulant or
NYC-WTC 000104861
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
No available related records indexed in this group.
NYC-WTC_000128550
Asbestos inspection report notification form submitted to NYC DEP for 102-104 Greenwich Street.
17 shared non-person entities · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000154680
Application form submitted to the Department of Environmental Protection for notification of an asbestos inspection project.
10 shared non-person entities · similarity 0.976
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000112116
NYC DEP emergency notification form documenting an urgent asbestos abatement situation at 250 Vesey Place requiring immediate action.
10 shared non-person entities · similarity 0.971
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000125579
Technical specifications document prepared for asbestos abatement work at the 130 Cedar Street site.
11 shared non-person entities · similarity 0.969
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000135560
Application for permits regarding exterior remediation work at World Trade Center vicinity buildings.
6 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155525
Initial draft of the comprehensive scope of work required to safely clean 114 Liberty Street following environmental damage.
14 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000098577
Contract specifications outlining site decontamination and asbestos disposal procedures for 53 Park Place.
9 shared non-person entities · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.965
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.965
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000107379
Formal request by a resident for the Department of Environmental Protection to perform cleaning and monitoring work at their apartment.
7 shared non-person entities · 1 shared topics · similarity 0.965
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000127792
NYC DEP Asbestos Project Notification form for abatement activities at a facility in the Phase 1 Decontamination Plan binder.
7 shared non-person entities · similarity 0.964
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000146129
Correspondence from NYC Corporation Counsel providing comments on excerpts of a draft EPA evaluation report regarding the WTC response.
Cited alongside this record in an Ask answer
NYC-WTC_000149199
Department of Environmental Protection advisory letter dated October 25, 2001, addressed to residents of Lower Manhattan.
Cited alongside this record in an Ask answer
NYC-WTC_000106110
Department of Environmental Protection advisory concerning air quality for building owners south of 14th Street following the WTC collapse.
Cited alongside this record in an Ask answer
NYC-WTC_000128550
Asbestos inspection report notification form submitted to NYC DEP for 102-104 Greenwich Street.
Cited alongside this record in an Ask answer
NYC-WTC_000142697
Report detailing air quality monitoring efforts and health precautions for residents regarding dust and smoke exposure.
Cited alongside this record in an Ask answer