Asbestos Inspection Report
Premise No. Inspection Date:
114 Liberty Street March 11, 2003
Floor Zip Borough Block Lot Squad # Badge #
All 10006 1 (Manhattan) 52 7502 N/A A019
Inspector Building Type Basis of Inspection Photos Taken
Penny Theodorellys
Contractor's Name
QS A WTC Unoccupied Bldg DEP Cleanup
Sample Number
No
ETS Construction, Inc N/A
Address City Sample Number
160 Clay Street, Brooklyn N/A
State Zip Phone Sample Number
NY 11222 (718)706-1032 N/A
Laboratory Name Owner's Name
JLC Environmental Consultants 114 Liberty LLC
Address City Address City
200 Park Avenue South, New York
State Zip Phone State Zip Phone
NY 10003 (212)420-8119
Contact Person Time of Inspection from:
11:30 A.M. — 12:30 P.M.
This inspection was the continued monitoring of the DEP clean-up activities at the site. All work to be
performed in accordance with contracts WTC-LBC and WTC-LBA. Clarifications and updates were provided to
the contractors and residents by e-mail. Copies of correspondence to be incorporated with these inspection
reports.
Contractor and Project Monitor representatives were present on site at my arrival. Also present were
representatives from local 78, who were holding a meeting with handlers.
An inspection of the work area was performed by Alphonso Plumptre, R. Rammohan, and I. The inspection
disclosed that house electric power was still on in some areas and that temporary power was also installed.
The temporary power had numerous locations where chords were not properly suspended and the bulbs were
not protected with cages. In addition, isolation barriers were coming loose in some locations. An access panel
was observed on the sixth floor that was not evident during earlier inspections. Mr. Aihem of ETS opened an
area adjacent area and disclosed the presence of a vertical duct and a pipe chase. These observations were
not evident in the architectural plans (structural and HVAC) submitted to the Department by building
representatives.
In areas where the ceiling was removed, Inspector Plumptre noted that the spray-on surfacing material did not
have a consistent appearance.
Corrective actions were addresses and contractor agreed to comply. Contractor was notified not to remove the
vertical ducts.
Upon return to the office, the building architect Mr. Chris Wamick was informed of the presence of the duct and
the instructions to the contractor. He stated that he too had seen the access panel during his walk through of
work progress. He did not provide information as to the function of the discovered duct.