Environmental Site Characterization — Facade Report
Fiterman Hall — 30 West Broadway, New York, NY
Airtek Project 05-0867 — January 10.2006
Physical Condition of Facade:
With the exception of the Gash Area, the Building facade is in excellent
condition. The brick fascia is intact, the newly installed window systems are in
excellent condition, and their rubberized caulking and sealing components are
intact.
3.4 Asbestos-Containing Building Material Inspection and Testing
Testing confirms that the brick, mortar, sluiced mortar, block and window sealant
materials (caulk & glazing) are non-asbestos materials. All other window
components are glass and aluminum, and are non-suspect. Asbestos-containing
facade materials include the interior vapor barrier that was applied to the original
facade, and lintel flashing that exists below the windows between the brick fascia
and the facade structural components (Please see Figure F-I Section View for
flashing location). ACBM testing data is included as Attachment B.
3.5 Lead-Based Paint Survey
Testing of facade components indicated that facade materials are not coated with
lead-based paint. Testing was conducted by X-Ray Fluorescence (XRF).
Destructive testing was conducted to allow access to all facade components.
Results of the lead testing conducted are included as Attachment C.
3.6 WTC COPC Impact Inspection
Surface Impact:
As noted above in Section 3.3, close visual inspection of the brick fascia and
window systems indicate that with the exception of the gash area, WTC debris
does not exist on the facade. Wipe testing confirms that levels of CoPCs detected
on the fascia are consistent with, or below levels that would be expected on a 60
year-old urban structure. As an example, the highest level of lead dust detected
above the ground floor was 8.18 ug/ft2. By law, at 39 ug/1t2 a school classroom
floor may be occupied by kindergartners. Similar results were exhibited in
sampling for other CoPCs. Metals wipe testing data is included in Attachment A.
Interstitial Impact
Interstices do not exist within the facade system except for the communicating
openings referenced in Section 3.1 above, the interior chases accessible from the
interior of the Building, an,d individual structural blocks which are not
compromised. The notable exception, of course, is the gash area, which will be
subject to focused cleaning.