Preservation Brief 7: The Preservation of Historic Glazed Architectural Terra-Cotta Page 8 of 14
emit heat--heat which can be measured in terms of infrared light. While infrared light cannot be seen by the human eye, it can be measured by infrared scanning. Infrared photography, a kind of infrared scanning, has been of particular use in detecting sources of heat loss in buildings in recent years. Broken or loose internal terra-cotta pieces have a less firm attachment to the surrounding firm or attached pieces and, therefore, have different thermal properties, i.e., temperatures. These temperature differences become evident on the infrared scan and may serve as a fair indication of internal material deterioration in terra-cotta.
Sonic testing has been successfully used for some time to detect internal cracking of concrete members. In the hands of an experienced operator, there are conditions where it can detect internal failure in glazed architectural terra-cotta. Sonic testing registers the internal configuration of materials by penetrating the material with sound waves and reading the patterns that "bounce back" from the originating source of the sound. Readings at variance with those from undeteriorated material might indicate collapsed webbing or pools of water in the interior of the terra-cotta unit.
Metal detection is a non-destructive and generally useful way of locating the position of internal metal anchoring. Metal detectors indicate the presence of metals by electromagnetic impulses. These impulses are transmitted onto an oscilloscope where they may he seen or they are converted to sound patterns which may be heard by the operator. Original drawings are eminently useful in predicting where internal metal anchoring should be. Metal detectors can confirm that indeed they are still there. Without original drawings, the contractor or architect can still locate the metal anchoring, however. No reading where an anchor would be expected could indicate a missing anchor or one that has seriously deteriorated. The information produced by metal detection is, at best, only rough. However, it is the most viable way of locating the internal metal anchoring without physically removing, thus irreparably damaging, the glazed architectural terra-cotta units themselves.
Laboratory analysis may be carried out on samples of removed original material to find glaze absorption, permeability or glaze adhesion, or to evaluate material for porosity. These tests are useful in determining the present material characteristics of the historic glazed architectural terra-cotta and how they may be expected to perform in the future.
Maintenance, Repair and Replacement Deterioration in glazed architectural terra-cotta is, by definition, insidious in that the outward signs of decay do not always indicate the more serious problems within. It is, therefore, of paramount importance that the repair and replacement of deteriorated glazed architectural terra-cotta not be undertaken unless the causes of that deterioration have been determined and repaired. As mentioned before, one of the primary agents of deterioration in glazed architectural terra-cotta is water. Therefore, water-related damage can be repaired only when the sources of that water have been Exposed or freestanding terra-cotta detailing eliminated. Repointing, caulking and replacement (parapets, urns, balusters, etc.) have traditionally of missing masonry pieces are also of primary been subjected to the most severe vicissitudes of concern. Where detailing to conduct water in the deterioration as a result of freezing temperatures and water. Photo: NPS files. original design has been insufficient, the installation of new flashing or weep holes might be considered.
Where stress-related or structural problems have caused the deterioration of glazed architectural terra-cotta, the services of a structural engineer should be sought to http://www2.cr.nps.gov/tps/briefs/briefU7.htm 10/3/2001
NYC-WTC 000093845
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000093852
Brief explaining risks of sandblasting and chemical treatments on historic building materials.
Same agency, volume and box · similarity 0.881
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000093728
Appendix B outlining performance standards and cleaning requirements for historic building exteriors.
Same agency, volume and box · similarity 0.854
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000093788
Fax transmittal from the Mayor's Office regarding a March 2002 meeting with the building group.
Same agency, volume and box · similarity 0.829
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000164903
Forwarded programmatic agreement documentation addressing post-disaster building cleaning procedures and eligible building list for recovery efforts.
Similar document embedding; no shared entity or topic indexed. · similarity 0.845
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000125098
Protocol document outlining air sampling and monitoring procedures for 130 Cedar Street.
Similar document embedding; no shared entity or topic indexed. · similarity 0.827
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000152327
A financial document from late September 2001 related to water supply operations and emergency response costs.
1 shared topics · similarity 0.825
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000150931
Cover fax from the Mayor's Office forwarding DEP documents regarding exterior clean-up to be reviewed before a meeting with building owners.
Similar document embedding; no shared entity or topic indexed. · similarity 0.824
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000166488
Department of Buildings report containing findings and recommendations regarding the World Trade Center site.
Similar document embedding; no shared entity or topic indexed. · similarity 0.821
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000153308
Draft advisory outlining required safety assessments and utility checks before allowing residents to return to buildings near the World Trade Center.
Similar document embedding; no shared entity or topic indexed. · similarity 0.818
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000139257
DEP official requests final review of the latest air monitoring Scope of Work to conclude negotiations.
1 shared non-person entities · similarity 0.817
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000128425
Document excerpt describing compliance requirements for environmental remediation work at 94 Greenwich Street.
Similar document embedding; no shared entity or topic indexed. · similarity 0.816
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000111934
Document outlining regulatory compliance and follow-up visual assessments conducted by DEP at buildings near the World Trade Center.
Similar document embedding; no shared entity or topic indexed. · similarity 0.815
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000093580
Archival reference document with minimal visible content related to WTC-era landmark information.
Filed in the same folder
NYC-WTC_000093581
Administrative record from the Landmark Information folder regarding the World Trade Center site.
Filed in the same folder
NYC-WTC_000093582
Administrative record from the Landmark Information folder regarding the World Trade Center site.
Filed in the same folder
NYC-WTC_000093583
Landmarks Preservation Commission notice withdrawing an application for alterations at 192 Broadway due to lack of landmark status.
Filed in the same folder
Permit for minor work issued by the Landmarks Preservation Commission for alterations at 55 Liberty Street.
Filed in the same folder