and yet permit emergency exiting. Exits shall be checked daily against exterior
blockage or impediments to exiting.
j) Temporary lighting within the Work Area and decontamination system shall be
provided as required to achieve minimum illumination levels.
k) Hand power tools used to drill, cut into, or otherwise disturb ACM shall be
equipped with HEPA filtered local exhaust ventilation.
1) Prior to being plasticized, the Work Areas shall be cleaned using HEPA vacuum
equipment and/or wet cleaning methods as appropriate. Methods that raise dust,
such as dry sweeping or vacuuming with equipment not equipped with HEPA
filters, shall not be used.
m) Plasticize the area after pre-cleaning and construction of hardwood barriers, using
the following procedures.
(1) Cover floors with one layer of 10-mil polyethylene sheeting, turning layer
a minimum of 6 inches up wall, and seal layer to wall.
(2) Cover walls on which removal will not take place, with one layer of 6-mil
polyethylene sheeting, overlapping wall layer a minimum of 6 inches, and
seal layer to floor layer.
(3) Cover floors with a second layer of 10-mil polyethylene sheeting, turning
layer a minimum of 12 inches up wall, and seal layer to wall.
(4) Cover walls on which removal will not take place, with a second layer of
6-mil polyethylene sheeting, overlapping wall layer a minimum of 12
inches, and seal layer to floor layer.
(5) The area above the Work Area shall be enclosed with two layers of 10-mil
reinforced polyethylene sheeting to facilitate the complete enclosure of the
Work Area and the maintenance of negative pressure within the Work
Area.
n) Pre-Removal Inspections
(1) Prior to removal of any ACM, the Contractor shall notify the Testing
Laboratory and request a pre-removal inspection. Posting of warning
signs, building of decontamination enclosure systems, and all other
preparatory steps have been taken prior to notification of the Testing
Laboratory.
(2) Contractor shall correct any deficiencies observed by Testing Laboratory
at no additional cost to City.
(3) Following the Testing Laboratory’s approval of the Work Area
preparations, removal of ACM may commence.