NYC 9/11 Public Portal Document
■
a 40 Rector Holdings, LLC
C/0 Tannenbaum Helpern Syracuse & Hirschtritt LLP
Ambient Air Sampling - 40 Rector Street
ATC Project No.: 19855-0001
October 25,2001
Page 3 Of 7
I custody forms and laboratory generated analytical data is included in Attachment 2 at
the end of this report. A summary of the data is provided in Table 2.
I Table 2 Summary of Ambient Air Sample Results
Floor Analytical Result Floor Analytical Result
I 1
2
No structures detected
No structures detected
10
11
No structures detected
No structures detected
I 3
4
5
No structures detected
No structures detected
No structures detected
12
14
15
No structures detected
No structures detected
No structures detected
I 6
7
No structures detected
No structures detected
16
17
No structures detected
No structures detected
a 8
9
No structures detected
No structures detected
18
19
No structures detected
No structures detected
a Based upon the analytical results recording levels within the AHERA clearance
requirement, it is ATCs opinion that the ambient air samples collected throughout the
building following the subsequent cleaning met an acceptable criterion for re-occupancy.
■ lAQ Evaluation
The lAQ evaluation included collection of real-time measurements of temperature,
relative humidity, carbon dioxide (CO,), carbon monoxide (CO), respirable particulates
and total volatile organic compounds (TVOC). Currently, there are no regulatory
I standards for indoor air quality in non-industrial buildings, such as offices and schools.
For the real-time data collected, ATC uses the commonly accepted guidelines cited in
the following publications:
I • Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American
Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
I •
•
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
a Table 3 on the following page lists target guidelines for the parameters that ATC
evaluated during this investigation.
a
a
a ATC Associates Inc. © 2001
CITY_21MC100__00708 7977
NYC-WTC_000437423