NYC 9/11 Public Portal Document
I ATC Environmental, Inc.
■ 104 East 25th Street
I ATC Associates Inc.
New York, New York 10010
Approved N.Y. State ELAP #10879
R 104 East 25th Street
New York, NY 10010
ACCREDITED NVLAP Lab Code #1187
Report Date; 09/29/01
« ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method: AHERA Final Rule, ERA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987
lH Sample Identification
Analysis Parameters
Proiect/Site: 40 Rector Street, NY, NY TEM Sample No.: 5579 - 59737
I Foors 6, 7, 3, 4, 11, 2, 1/Lobby
Date Received: 09/29/01 Grid Openings Analyzed? 6
Project Sample No.: T14 Average Grid Opening; 106.00 um
I Air Volume; 126Q liters Total Area Analyzed; 0.0674 mm2
I Filter Type: MCE 25 mm diam., Pore Size; 0.45 um
Effective Area; 38S mm2
Analytical Sensitivity; 14.8 s/mm2
0.0045 s/cc
H FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
I Singlie
Fibers Bundles Clusters
Matrix
Struct.
Total.
Struct
Struct.
>=5um
Filter
Struct/inTn2 Struct/cc
Air
ngm/mS
im Chrysotile Asbestos 0 0 0 0 D 0 0.0 0.0000 0
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
lH Ambiguous
0 0 0 0 0 0 0.0 0.0000 0
Total asbestos (includes ambiguous structures) 0 0 0.0 0.oooo 0
I N6n-Asbestos
No Identification
0
0
0
0
0
0
0
0
0
0
0
Q
0.0
0.0
0.0000
0.0000
N/A
N/A
I Totals (All Structures) 0 0 0.0 0.0000 N/A
The estimated uncertainty of this analysis is 1 standard deviation.
Non-asbestos fiber i.d. (EDS/SAED): None detected
H Amphibole Asbestos Type: None detected
__ _ __ _ ___________________________________________________
The Analysis was carried out in accordance with the approved TEM method.
I This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
I
Marek Peysakhov Michael A. Gorycki, Ph.D.
I Director of Electron Microscopy
I■f
CITY_21MC100_007087988
NYC-WTC_000437434
OCR can misread numbers and units. Confirm readings against the page image before using them.