Summary of work performed at the aforementioned facility from July 14 through August
26,2002:
1. Cleaning and Testing of Unit Ventilators
KCI performed environmental cleaning of all wall and ceiling mounted Unit Ventilators
within the facility. This cleaning work was performed within tent enclosures under
negative pressure. Each Unit Ventilator was visually inspected by TEG and if found to
be Tee of visible dust/debris a wipe sample was collected fi-om the Unit Ventilator to be
tested for lead. If sample results indicated a lead concentration exceeding the NYC
Board of Education/NYC School Construction Authority (“NYC SCA”) clearance levels
then the Unit Ventilator was recleaned and retested.
Air Monitoring-
During the cleaning of the Unit Ventilators within each tent enclosure, TEG performed
personal (OSHA) air monitoring on KCTs personnel working within each tent, in
addition to ambient area monitoring outside each tent. Personnel and area samples were
analyzed for lead via NIOSH Method 7082.
2. HVAC System Wipe Sample Testing
At the conclusion of all HVAC/Duct cleaning (performed by the HVAC Cleaning
Contractor) on each floor, TEG collected wipe samples fi-om the return and supply ducts
within each zone to be analyzed for lead via EPA Method SW846-7420.
In addition wipe samples to be analyzed for lead were collected from the air handling
units for HVAC systems one (I) through fifteen (15) after they had been cleaned by the
HVAC Cleaning Contractor.
3. General Cleaning
At the conclusion of all Unit Ventilator and HVAC/Duct related cleaning work on each
floor of the facility, KCI performed general cleaning of the Unit Ventilators in each
functional space on the entire floor. At the conclusion of the general cleaning a visual
inspection was performed by TEG and a representative fi-om the NYC SCA. If the visual
inspection was successful then TEG collected two (2) wipe samples fi-om each functional
space (room/corridor, etc.) to be analyzed for lead via EPA Method SW846-7420.
4. Final Clearance Air Monitoring
At the conclusion of all the aforementioned work performed on floors three (3) through
ten (10) final clearance air monitoring was performed according to the following table;
Sample Type Analytical Methodology Number of Samples
Collected Per Floor
Airborne Asbestos Transmission Electron Microscopy 10
AHERA Protocol
Airborne Lead NIOSH 7082 5
All final clearance air monitoring was performed using aggressive techniques.