Asbestos TEM analysis, World Trade Center, Sep 2001

Machine-extracted title · confidence 44%

TEM-based asbestos analysis for World Trade Center site, 09/17/01.

NYC-WTC_000431345
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street I New York, New York 10010

NYC School Construction Authority Approved N.Y. State ELAP #10879 30-30 Thomson Avenue ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 09/17/01

ASBESTOS FIBER ANALYSIS BY TRj\N5MISSION ELECTRON MICROSCOPY (TEM) I With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDSl Method; AHERA Final Rule, EPA Federal Register (40 CFR, Part 7G3), Vol. S2, No. 210, October 30, 1987

I Sample Identification Analysis ParameCers

Project/Site; Morld Trsde Center,NYj^ TEM Sample No.; SSLS - 590S0 Personal Monitoring Date Received: 09/17/01 ' Grid Openings Analyzed: 10

Project Sample No.: 031 Average Grid Opening: 106.00 um

Air Volume; 490 liters Total Area Analyzed: 0.1124 mm?

Filter Type: MCE 25 mm diam., Pore Size; 0.45 um Analytical Sensitivity: 6.9 s/mm2 Effective Area: 385 mm2 0.0071 s/cc

FIBROUS PARTICULATES ANALYZED Nufnber Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct. > = 5um Struct/mm2 Struct/cc nqm/ml

I Chrysotile Asbestos 3 4 1 3 11 3 97.9 0.078S 2590

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0 I Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) 11 3 97.9 0.0785 2590

I Non-Asbestos No Identification 0 0 0 0 0 . 0 0 0 0 0 0 0 0.0 0.0 0.0000 0.0000 N/A N/A

I Totals (All Structures) The estimated uncertainty of this analysis is 1 standard deviation. 11 3 97.9 0.Q785 N/A

B Non-asbestos fiber i.d. (EDS/SAED) : None detected I Amphibole Asbestos Type: None detected

.The Analysis was carried out in accordance with the approved TEM method. I This laboratory is in compliance with the quality specified for the' method.

Analyzed by: I Report Reviewed by:

Marek Peysakhov. Michael A. Gorycki, Ph.D. I Director of Electron Microscopy

CITY_21MC100_010237402

NYC-WTC_000431345

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000431345Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →