Washdown request for AMEX Building, FEMA funds

Machine-extracted title · confidence 40%

Request for FEMA funding review to finance cleaning of AMEX Building (200 Vesey).

NYC-WTC_000416719–000416737
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

GPS Enviroitmental Consultants, Inc.

A GPS NYC Asbestos Investigator collected fourteen bulk samples of gross debris on September 19, 2001 from representative locations within the building to assess the amount of asbestos contamination resulting from the event. Analyses indicated that asbestos containing materials were detected in bulk samples collected from the debris. Based upon these results and in an effort to protect the health and safety of people involved in the cleanup project and to obtain a building acceptable for rc-occupancy, a licensed asbestos abatement contractor, using certified asbestos handlers was employed by Meirill Lynch to clean the entire building using asbestos specific procedures.

The cleanup project was divided into three phases with the first phase, Phase 1, beginning on September 24, 2001. The final phase. Phase Hl, was completed and final air sampling collection completed on January 21, 2002.

Phase 1 cleanup operations were performed by Pinnacle Environmental Coi-poration throughout the building in conrorrriance with acceptable asbestos work practices.

Phase H fine cleaning operations were performed by PMS Castrophe utilizing asbestos abatement handlers for cleaning operations.

The HVAC duct system was separately assessed for asbestos and lead contamination by Tri Dim Coi-poration on October 19, 2001. Samples were collected from the HVAC duct system on the C levels, 3”* and 9^ floors and analyzed for asbestos and lead content. No asbestos or lead was detected in the areas tested, although visual inspection indicated that the system was contaminated with fine particles. The particulate content was above the N.ADCA Standard Level of Cleanliness in 29 of 33 areas tested, A HVAC duct cleaning company was employed by Menill Lynch to clean the HVAC system from the C levels through the 22"'^’ floor. HV.AC cleaning was performed by KASCO using certified asbestos workers. The cleaning procedures arc outlined in section 3.0. A separate closeout report was issued by Kasco,

3.0 Abatement and Cleanup Activities

A NYC Investigator collected 14 bulk samples from representative floors on the east side of the facility where windows were broken and bulk/gross debris was observed. The samples were analyzed using the PT.M, (polarized light Micro.scopy) analytical technique. Three Samples on three separate floors had results of asbestos present in amounts greater than 1%, Based on these results all bulk/ginss material was treated as asbestos containing material, (ACM). The east side of facility from the street level through floor 22 was most heavily damaged with many broken windows and large amounts of debris. Floor 23 and above exhibited much less damage having fewer broken windows.

Merrill lynch, Worl.fi Fmcmcutl Center, South Tower, 225 Liberty Street, New York, NY Page 2

11533

CITY_DEP_HILLMAN_SUBP_000005157

NYC-WTC_000416731

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000416731Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →