§1-91 TITLE 15—DEPT. OF ENVIRONMENTAL PROTECTION
(2) the decontamination systems shall be sealed airtight after the evacu
ation of workers and/or authorized visitors from the work area, and
(3) all adj acent areas shall be monitored for asbestos fiber concentration
upon discoveiy of, and subsequently throughout, the power failure.
(g) Negative pressure ventilation equipment shall be installed and oper
ated to provide at least one air change in the work area every 15 minutes,
except during clearance air monitoring when at least one air change in the
work area every 30 minutes shall be provided.
(continued')
5842 RCNY 5-31-98