Mr. Bernard P. Orlan June 13, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)___________ _ ATC Project No. 15-19125-0246 Real-Time Environmental Measureme.nts

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:45 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.1 °F to 76.5 °F. Thirty-one (31) of the indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature was 78.3 to 79.6 °F.

Relative Humidity

The relative humidity indoors ranged from 55.8 percent to 67.8 percent. Eighty-three (83) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 75.4 and 79.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 516 ppm to 1194 ppm. Twenty-six (26) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 388 ppm and 396 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1096 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for both readings.

Respirable Particulates (PM2^3)

Respirable particulate concentrations* indoors ranged between 25 pg/m^ to 39 pg/m^ with an average of approximately 30 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 48 and 58 Pg/m3.

CITY_21MC100_003797732

NYC-WTC_000406972

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406972Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335940

Indoor air quality measurements report for Stuyvesant HS, June 2002.

Similar indexed content

NYC-WTC_000335929

Indoor air quality measurements report for Stuyvesant HS, June 2002.

Similar indexed content

Compare copies and versions →