Indoor air quality report, Stuyvesant HS, May 2002

Machine-extracted title · confidence 28%

ATC IAQ measurements collected on May 23, 2002 for Stuyvesant High School.

NYC-WTC_000372973–000372977
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 24. 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_____________ ATC^roiectNoM5-19I25-0246 Real-Time Environmental Measureme.nts

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 10:20 A.M. and concluded after 2:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69 °F to 73.7 °F. One hundred and five (105) of the indoor measurements were below and thirteen (13)-were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature range was 63.4 to 67.6°F.

Relative Humidity

The relative humidity indoors ranged from 30.1 percent to 38.7 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 32.6 and 34.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 426 ppm to 1183 ppm. Six (6) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 380 ppm and 426 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1126 ppm (background level + 700 ppm). The highest reading was taken in room 1006 at 2:00 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm on both readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 12gg/m^ to 22 pg/m^ with an average of approximately 17 pg/m^. None of the indoor measuicments were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensiti^’e individuals and children. The outdoor respirable particulate concentrations were 29 and 32 pg/m^.

CITY_21MC100_002868664

NYC-WTC_000372975

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000372975Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000213072

Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 16, 2002.

Similar indexed content

Compare copies and versions →