ATC IAQ measurements collected March 8–12, 2002 at Stuyvesant HS.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗March 8, 2002 IAQ measurements report for Stuyvesant High School.
NYC-WTC_000402161–000402164OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 11, 2002 Indoor Air Quality Measurements . Page 4 Stuyvesant High School fM477) ATC Project No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms-327, 333, 638 and 740. The PM2.5 concentration range for these rooms as follows Room # 327 17 - 22 pg/m^. Room # 333 14-18 pg/mA Room # 638 7-14 pg/m^, Room # 740 7-15 pg/m^, with an average of approximately 20, 16,10, 11 pg/m^ respectively..
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
T70C Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment,,ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of temperature and concentrations CO, and TVOCs, were within applicable standards and guidelines. 2. Fifty-four (54) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. One (1) CO2 measurement was above the range recommended by ASHRAE 62-1999. All others were below the maximum concentration. 3. One (1) of the outdoor respirable particulate measurements was above the EPA recommended guideline for children and sensitive individuals of 40 pg/m^.
It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext # 356 or 212
Sincerely, ATC ASSOCIATES INC. Reviewed by:
Prasad Doddapaneni James R. Cohn, CIH, CSP Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002923651
NYC-WTC_000402164
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000336395
ATC IAQ measurements collected March 8–12, 2002 at Stuyvesant HS.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402156
ATC IAQ measurements report for Stuyvesant High School dated March 2002.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270022
ATC IAQ measurements conducted March 14, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229527
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000269995
March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406600
April 22, 2002 memo documenting IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336077
May 2002 indoor air quality measurements at Stuyvesant High School, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336433
Indoor air quality measurements collected for Stuyvesant High School by ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336395
ATC IAQ measurements collected March 8–12, 2002 at Stuyvesant HS.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402156
ATC IAQ measurements report for Stuyvesant High School dated March 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336102
Indoor air quality measurements conducted May 14, 2002 at Stuyvesant High School.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402186
ATC indoor air quality measurements at Stuyvesant High School, March 13, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270058
ATC IAQ measurements collected March 25, 2002 at Stuyvesant High School for NYC BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336377
IAQ measurements collected at Stuyvesant High School; March 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000336395
ATC IAQ measurements collected March 8–12, 2002 at Stuyvesant HS.
Similar indexed content
ATC IAQ measurements report for Stuyvesant High School dated March 2002.
Similar indexed content
NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
Similar indexed content
NYC-WTC_000270022
ATC IAQ measurements conducted March 14, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.
Similar indexed content