Mr. Bernard P. Orlan March 14, 2002
Indoor Air Quality Measurements Page 4
Stuyvesant High School CM477) ATC Project No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency
Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5
concentration range for these rooms was 9-17 pg/m^ with an average of approximately 14
Pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOCConcentrqtion
TVOCs inside the building were 0.0 ppm to 0.1 ppm The outdoor TVOC concentrations were 0.2
ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO ,CO2, and TVOCs, were within applicable
standards and guidelines.
2. Fourteen (14) measurements of relative humidity were below the ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
3. Three (3) temperature measurements were below the range of 68 to 75°F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this, report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
ATC ASSOCIATES INC.
Reviewed by:
< Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment