NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Stuyvesant High School, Mar 2002

Machine-extracted title · confidence 59%

ATC IAQ measurements report for Stuyvesant High School dated March 2002.

NYC-WTC_000402156–000402159
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 8, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 6-14 pg/m^ with an average of approximately 10 Pg/m3,

* The measurements made during this assessment were instantaneous readings, the NPAAQS is ■ a 24-hour average.

TVOCConcen^tion

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDING

Based on the real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations CO, and TVOCs, were within applicable standards and guidelines. 2. One hundred and sixteen (116) measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. One (1) CO2 measurement was above the range recommended by ASHRAE 62-1999. All others were below the maximum concentration. 4. One (1) of the outdoor respirable particulate measurements was above the EPA recommended guideline for children and sensitive individuals of 40 pg/m3.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 21 lor 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

Yiannis Efstatmou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002923633

NYC-WTC_000402159

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000402159Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000269995

March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).

Similar indexed content

Compare copies and versions →