Indoor air quality report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 39%

ATC IAQ measurements report for Stuyvesant High School dated January 2, 2002.

NYC-WTC_000401735–000401738
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th Street New York, New York 10010 WWW atc-enviro.com 212.353.8280 Fax 2-12.353.8306 ASSOCIATES INC.

January 3-, 2002

Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-1.1 Queens Plaza North Long Island City, NY-] I 101-4008

Re: Indoor Air Quality Assessment Stuyvesant High School (M477) 345 Chambers Street New York, New York 10007 ATC Project No. 15-19125-0246

, Dear Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on January 2, 2002, at the referenced school. The New York City Board .of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained. , .

SCOPE OF WORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dio.tide (CO,) and carbon mono.vide (CO).

Total volatile organic compounds (TVOCs) and respirable particulates were also measured.

Jimmy Choy, Industrial Hygienist, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551, manufactured by TSI. Inc.

ATC measured concentrations of respirable particulates (PMo 5) with a Dust-Trak® Aerosol Monitor Model 8520. manufactured by TSI, Inc.

ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and

CITY_21MC1OO_OO2897684 NYC-WTC_000401735

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401735Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000401739

Indoor air quality report for Stuyvesant High School, January 2002.

Similar indexed content

Compare copies and versions →