NYC 9/11 Public Portal Document
104 East 25th St., 10th Floor
New York, New York 10010
www.atc-enviro.com
212.353.8280
Fax 212.353.8306
ASSOCIATES INC.
March 29, 2002
Mr. Bernard P. Orlan
Director, Environmental Health and Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101
Re: Air Sampling for Hydrocarbons
Stuyvesant High School
ATC Project No. 15-19125-0246
Dear Mr. Orlan:
ATC Associates, Inc. (ATC) is pleased to provide this letter report of air sampling for
hydrocarbon compounds conducted on March 13, 2002, at the referenced school. The New York
City Board of Education (BOE) requested this sampling at the recommendation of H. A. Bader, a
consultant to the parents’ association.
SCOPE OF WORK
ATC collected three (3) samples for hydrocarbon compounds (HC) at specified locations.
Samples were collected for a minimum of seven (7) hours using activated coconut shell charcoal
tubes connected to battery-powered sampling pumps at a flow rate of 0.2 liters per minute.
Pumps were calibrated before and after each sampling period. Two (2) samples were collected
inside the building and one (1) was collected on the roof. One blank tube was also submitted.
The samples were sent to PSC Analytical Services, Inc., an American Industrial Hygiene
Association-accredited laboratory in Reading, PA. Analysis was performed by capillary gas
chromatography/flame ionization detection (MOSH Methods 1003, 1005, 1022, 1300, 1500,
1501). .
Each sample was analyzed for a panel of sixteen (16) specific HC compounds. These compounds
were: pentane, acetone, methylene chloride, hexane, chloroform, methyl chloroform, benzene,
1,2-dichloroethane, trichloroethylene, toluene, perchloroetyhylene (tetrachloroethylene),
chlorobenzene, ethylbenzene, styrene, cumene and xylenes. In addition, two non-identified
peaks, total other A- hydrocarbons and total other B-hydrocarbons, were reported. The A-
hydrocarbons are those, such as gasoline or light alcohols, with boiling points less than that of
benzene (176“F). The B-hydrocarbons are those, such as mineral spirits or petroleum naphtha,
with boiling points greater than that of benzene. A copy of the analytical report is attached
The sampling locations were the P' floor lobby, 2"^ floor bridge entrance lobby and the roof.
CITY_21MC100_002897178
NYC-WTC_000401361
OCR can misread numbers and units. Confirm readings against the page image before using them.