Mr. Bernard P. Orlan May 7,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environ.MENTAL Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 67.4 °F to 73.6 °F. Forty-seven (47) of the indoor measurements collected were below and two (2) indoor measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 67.4 °F to 73.6 °F.
Relative Humidity
The relative humidity indoors ranged from 45.5 percent to 52.3 percent. AU the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 47.1 to 49.7 percent.
CqrbonDioxideCpncentration
Carbon dioxide concentrations indoors ranged from 401 ppm to 1021 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 481 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1181 ppm (background level + 700 ppm). The highest reading (1021 ppm) was measured in room # 706 around 10:35 A.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings..
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 18 pg/m^ to 32 pg/m^ with an average 25 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the outdoor instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
CITY_21MC100_002891354
NYC-WTC_000396452
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396531
Measurements collected May 14, 2002; BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384886
IAQ report covering measurements at HS Economics and Finance, 100 Trinity Place.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223580
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396474
Indoor air quality measurements collected May 8, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396591
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396675
IAQ data with TVOCs, CO, and particulates for Trinity Place site, Jun 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384975
ATC IAQ measurements at 100 Trinity Place (HS of Economics and Finance) for BOE in May 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similar indexed content
Measurements collected May 14, 2002; BOE monitoring.
Similar indexed content
IAQ report covering measurements at HS Economics and Finance, 100 Trinity Place.
Similar indexed content
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 7, 2002.
Similar indexed content
ATC indoor air quality measurements collected May 14, 2002.
Similar indexed content