Mr. Bernard P. Orlan April 30, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below. ,
Temperature.
Indoor dry bulb temperature measurements ranged from 71.2 °F to 76.9 °F. Forty-three (43) of the indoor measurements for temperature were below and eighty-five (85) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season . The outdoor temperature ranged from 63.2 to 66.9 °F.
Relative Humidity
The relative humidity indoors ranged from 23.3 percent to 31.2 percent. One hundred and seven (107) of the indoor measurements for relative humidity were below and twenty-one (21) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 23.6 to 28.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 457 ppm to 1346 ppm. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 596 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1296 ppm (background level + 700 ppm). The highest measurement (1346 ppm) was collected in room 905 at 10:30 AM with 34 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was Ippm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 17 pg/m^ with an average 12 pg/m^- All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 6 pg/m^ to 38 pg/m^ with an average of 27 pg/m^. * "Hie measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002918788
NYC-WTC_000394888
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296762
ATC IAQ measurements report for HS for Leadership & [name], Apr 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394764
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394783
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000380933
Indoor air quality measurements at H.S. for Leadership & [name] as part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292020
ATC IAQ measurements collected June 24, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296785
ATC IAQ measurements at 90 Trinity Place; report dated Apr 17, 2002; project 15-19125-0290.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291705
Indoor air quality report for High School for Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399290
Indoor air quality measurements collected May 8, 2002, at the referenced school for BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements at the referenced HS, BOE request.
Similar indexed content
ATC IAQ measurements report for HS for Leadership & [name], Apr 15, 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similar indexed content