NYC 9/11 Public Portal Document
JLC ENVIRONMENTAL CONSULTANTS, INC.
200 Park Avenue South, Suite 1001, New York, New York 10003
Phone: (212) 420-8119 Fax: (212) 420-6092
Project No.: 01-2089003
Rose Associates Inc. ELAP Lab Code 11029 Analyte: FIBERS
200 Madison Ave. Sth Floor NIOSH and AIHA Lab Code; 100273 Date Received- 10/19/2001
New York. NY 10016 NVLAP Lab Code- 101953 Date Analyzed. 10/19/2001
Batch#: 0110A792
SUMMARY OF ANALYTICAL RESULTS
Site: 21 West Street, New York, NY
SAMPLE #
COLLECTED DESCRIPTION I LOCATION TIME(min) VOLUME(I) FIB/FIELO RESULTS(f/cc)
LAB#
001 Ambient/ PH Floor/ PH D in the North Section of 120 1846 3/100 <0.001 <LOD
iO-Octubei the Living Room
A 8042
002 Ambient/ PH Floor/ Hallway Between PH B and 120 1846 2/100 <0.001<LOD
18-October PHC
A 8043
003 Ambient/ 27th Floor/ Room 27 B at the North 120 1846 2/100 <0.001 <LOD
18-October Section of the Living Room
A 8044
004 Ambient/ 27th Floor/ Hallway Between Rms 27 D 120 1846 3/100 <0.001<LOD
16-October and 27 E
A 8045
005 AmbienV 22nd Floor/ Rm 22E/ At the North 120 1846 3/100 <0.001<LOD
18-Oetober Section of the Living Room
A 8046
006 Ambient/ 22nd Floor/ Hallway Between Apt. 22G 120 1846 2/100 <0.001<LOD
18-October and 22 H
A 8047
Sample Analysis by: <LOD = Less than limit of detection which is 5 5 Fibers/100 Fields
VOID1 = H.C P. (High Concentration of Particles)
Positive Phase Contrast Microscopy (PCM)
VOID2 = Overloaded
Method of Sample Preparation and Analysis >
All samples analyzed in accordance with the NIOSH 7400 Method using "A" Counting Rules Issue 2, August 1994
Instrumentation: c: '—•—iQrpk I k U < v>.
Olympus PCM Model BH-2 with Walton-Beckett Graticule (100um field diameter).
Guiam Machhiwala
Laboratory Director
Report Date: October 23, 2001
JLC is responsible for only the fiber counts within the limitations of the method described as NIOSH 7400 Among other limitations, this
method gives only an index of airborne fibers and provides only an estimate of asbestos concentration. Any and all claims arising out of
JLC's analysis of these samples are limited in recovery to the cost of analyzing samples. JLC accepts no other liability and the client agrees
to seek no costs beyond the above.
Page 1 of 5