Indoor air quality guidelines, Table 1

Machine-extracted title · confidence 46%

Table of target guidelines for IAQ parameters; DOAS/KAM consultant reference.

NYC-WTC_000385959–000385960
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P Chian Date. 2002 Indoor Air Qi.iality Assessment Pages F.S, XXX fBorougbl ATC Project No, 15-19125-XXXX

Tabic 1 lists target guidelines for the parameters that ATC evaluated dtinng this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

T.4BLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

aglScyorC

Carbon Dioxide <700 parts per million (ppm) (CO2) above background level ASHRAE 62 (also cited as <1,000 ppm) Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable Particles 50 -micrograms per cubic meter ASHRAE 62 (adoplcd Lorn (PMio) of air (ug/m^) annual average USEPA NPzVAQS) 150 pg/m^ 24-hoiir average Temperatoe Summra; 33-78.5 T at 60% RH ASHRAE 55 Winter: 69-76“F at 30% RII Relative Humidity 30 - 60 % ASHRAE 5.5 Total Volatile 1 ppm Organic Compo'osids i AHA (TVOC) I • Indoor locations positive ATC recommendation based on Relative t relative 10 outdoor the principle of keeping stale, Pressurization • Restrooms negative relative odorous or dirty air ton to all siUTOimdiug areas entering occupant spaces. • Offices positive relative to > corridors and common areas USEPA = United States Environmental Protection Agency NTAAQS = National Primary Ambient-Air Quality Standard AIKA = American Indusfr'al Hygiene Association

For purposes of evaluating the ATC used either the American Conference of Goverarnental Industrial Hygienists® (ACGIH) Threshold Limit Values® (TLVs*) or the Occupational Safety and Heaitli Administration (OSHA) Permissible Exposure Limits (PELs), The ACGIH TLVs are independent, consensus, guidelines to be used in the evaluation and control of health hazards in the industrial workplace The TLVs refer to the airborne concentrations of substances, and the conditions under which it is believed that the majority of indushial workers may be repeatedly exposed, day after day, without adverse effect. It should be noted that a small nuTriber of individuals might be susceptible to discomfort at levels below the TLV. Therefore, the TLVs should not be regarded as a definitive line between healthful and unhealthful conditions.

COO® OlV 9OC8 esc CTC IVJ rC-fT Z002/ZT/X0 CITY_21MC100_002836230

NYC-WTC_000385959

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385959Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311687

Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →