Mr. Bernard P. Orlan June 4, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (MS33)________ ATC Project No. 15-19125-0291 Real-Time environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Te^e^ure
Indoor dry bulb temperature measuremrats ranged from 74.8 °F to S2.5 °F. Eighty (80) of the indoor measurements for temperature were above and fourteen (14) of the measurements were within the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 'Fhe outdoor temperature measurements ranged from 71.9 °F to 79.0 °F.
Relative Httmidity
The relative humidity indoors ranged from 23.1 percent to 39.6 percent. Nineteen (19) of the indoor measurements for relative humidity bellow the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 22.3 to 28.4 percent.
CarionDioxideConcentratiqn
Carbon dioxide concentrations indoors ranged from 486 ppm to 1307 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 573 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1273 ppm (background level + 700 ppm). The highest concentrations were recorded in room 307 at about 12:29 PM with 20 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm.
Respirable Particulates (PM^j)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 26 pg/m^ with an average of 8 pg/m^- None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 15 pg/m3 to 66 pg/m^ with an average of 35 pg/in^ •
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
CITY_21MC100_002882398
NYC-WTC_000385073
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384991
ATC indoor air quality measurements at the referenced school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396675
IAQ data with TVOCs, CO, and particulates for Trinity Place site, Jun 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396591
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404586
IAQ report for High School of Economics and Finance (M833) dated May 1, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396671
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384975
ATC IAQ measurements at 100 Trinity Place (HS of Economics and Finance) for BOE in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396474
Indoor air quality measurements collected May 8, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259487
ATC summary of IAQ measurements collected June 4, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259483
ATC IAQ report documenting measurements collected June 3, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259547
ATC indoor air quality measurements at the referenced school, June 26, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similar indexed content
ATC indoor air quality measurements at the referenced school, May 2002.
Similar indexed content
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
Similar indexed content
IAQ data with TVOCs, CO, and particulates for Trinity Place site, Jun 2002.
Similar indexed content
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
Similar indexed content