Indoor air quality report, PS 89M, Mar 2002

Machine-extracted title · confidence 41%

ATC report of IAQ measurements collected at PS 89M for BOE evaluation.

NYC-WTC_000383889–000383892
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 21,2002 Indoor Air Quality Assessment Page 4 P,S89M ATC Project No. 15-19125-0297 concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 16 to 19 pg/m^ with an average of 18 pg/m3.-

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCConcer^qtior^

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment, • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debns.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were below applicable standards and guidelines, 2. All of the indoor measurements for temperature were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Thirty-seven (37) of the indoor measurements for relative humidity were below the ASHRAE-recoramended range of 30 to 60 percent for occupant comfort. 4. Three (3) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212.

Sincerely, Reviewed by: ATGASSOCL4TESil^^ -

CYiannis Efstathiouv James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002880989

NYC-WTC_000383892

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000383892Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS89M, Mar 2002

NYC-WTC_000383816

Indoor air quality measurements collected March 11, 2002 at PS89M for BOE evaluation.

Similar indexed content

Compare copies and versions →