Mr. Bernard P. Orlan March 26, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
individuals and children. The outdoor respirable particulate concentration measurements ranged
from 14 to 19 pg/m^ with an average of 17 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TyOCCotwentra^ns
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO, and TVOCs were below the applicable
standards and guidelines.
2. Four (4) of the CO2 measurements were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level.
3. All of the indoor measurements of relative humidity were below the ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
4. All indoor temperature measurements were within the range of 68 to 75°F (at 50 percent
relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating
season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely, Reviewed by:
A TC ASSOCIA TES INC.
Yiannis Efstathiou James R. Cohn, CH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_000623902
NYC-WTC_000400306