Mr. Bernard P. Orlan March 21, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATCProiect No. 15-19125-0297

Real-Time Environmental measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:30 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.5 °F to 73.8 °F. All of the indoor measurements for temperature were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 41.6 to 45.9 °F.

Relative Humidity

TTie relative humidity indoors ranged from 26.4 to 35.5 percent. Thirty-seven (37) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 40,3 to 45.9 percent.

CarbonDipxide Concentration

Carbon dioxide concentrations indoors ranged from 458 ppm to 1320 ppm. Three (3) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 435 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1135 ppm (background level + 700 ppm). The highest reading (1320 ppm) was measured in room 510 with 16 occupants around 9:00 AM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 17 pg/m^. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 11 pg/m^. AU of the seventy (70) instantaneous indoor readings were below the USEPA recommended

CITY_21MC100_002880988

NYC-WTC_000383891

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000383891Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS89M, Mar 2002

NYC-WTC_000383816

Indoor air quality measurements collected March 11, 2002 at PS89M for BOE evaluation.

Similar indexed content

Compare copies and versions →