Mr. Bernard P. Orlan March 22, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ArCPrpiectNpM5U9125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.9 °F to 75.3 °F. Six (6) of the indoor measurements for temperature were above the range of 68 to 75 °F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 49.4 to 50.6 °F.

Relative Humidity

The relative humidity indoors ranged from 21.9 to 31.7 percent. Sixty-three (63) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 23.4 to 24.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 428 ppm to 1338 ppm. Five (5) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 390 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1090 ppm (background level + 700 ppm). The highest reading (1338 ppm) was measured in room 510 with 28 occupants around 11:30 AM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 37 pg/m^. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 24 pg/m^. All of the seventy (70) instantaneous indoor readings were below the USEPA recommended

CITY_21MC100_000623866 NYC-WTC_000400278

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000400278Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →