Mr. Bernard P. Orlan April 11, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:06 A.M. and concluded after 2:51 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 67.2 °F to 77.5 °F. Four (4) of the indoor measurements for temperature were below, twenty one (21) measurements were above, and sixty-three (63) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 53.2 to 64.9 °F.
Relative Humidity
The relative humidity indoors ranged from 28.1 percent to 42.8 percent. Sixteen (16) of the indoor measurements for relative humidity were below and seventy two (72) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 53.2 to 64,9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 366 ppm to 1460 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 574 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1274 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. The highest levels of CO2 were detected in Gymnasium and Stair case A 7th floor were 1460 ppm, 1353 ppm respectively. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 0 to 4 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 ppm to 4 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 35 pg/m^ with an average 11 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 5 pg/m^ to 56 pg/m^ with an average of 25 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
CITY_21MC100_002879792
NYC-WTC_000383078
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259176
Indoor air quality report for the High School of Economics and Finance, April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402546
Indoor air quality measurements collected March 26, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402550
Indoor air quality measurements collected March 27, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384125
Indoor air quality report for school, measurements and professional signatures.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384258
Chain-of-custody document for potable water samples collected at 104 East 25th Street.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384254
Chain-of-custody for potable water samples taken at 104 East 25th Street location.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402451
ATC IAQ measurements report for High School of Economics and Finance, 100 Trinity Place, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402437
IAQ measurements conducted March 11, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259176
Indoor air quality report for the High School of Economics and Finance, April 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402495
Indoor air quality measurements collected on March 15, 2002 for the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259111
Indoor air quality measurements submitted to BOE for the High School of Economics and Finance, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384125
Indoor air quality report for school, measurements and professional signatures.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
Similar indexed content
NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
Similar indexed content
Indoor air quality report for the High School of Economics and Finance, April 2002.
Similar indexed content
NYC-WTC_000402546
Indoor air quality measurements collected March 26, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000402550
Indoor air quality measurements collected March 27, 2002 at the referenced school.
Similar indexed content